Fluke 4920613 Description
An optimized user interface, flexible current probes, and intelligent measurement verification function that allows you to digitally verify and correct connections makes setup easier than ever and reduces measurement uncertainty. Minimize your time in potentially hazardous environments and reduce the hassle of suiting up in PPE by using a wireless connection (WiFi) to view data directly in the field. Auto-configuration check ensures every measurement campaign is right, the first time. Power the instrument from the measured line to simplify the connection process.
Fluke 4920613 Includes
- (1) Flexible Current Probe
- (1) USB Stick
- (1) USB Cable
- (1) 3PHVL-1730 3-Phase + Neutral Voltage Test Lead
- (1) Test Lead Set Red/Black 0.18m
- (1) Test Lead Set Red/Black 1.5m
- (4) Alligator Clips
- (1) 173x/174x Soft Case
- (1) Cable Marker Kit
Fluke 4920613 Features
- Measure all three voltage and current phases plus the neutral current
- Comprehensive logging
- Measure with premium accuracy
- Capture dips, swells and interruptions
- Measure key power quality parameters
- Optimized user interface
- Flexible power supply
- Rugged and reliable
- Two external USB ports
- Ethernet connectivity
- Compact size
- Highest safety rating in the industry
- Optimized measurement accessories
- “In-workshop” or “in-the-field” setup and download through PC application software: simple download using USB memory stick, WiFi download, wired ethernet connection or via USB cable
- Energy Analyze plus application software: download and analyze every measured detail of energy consumption and power quality state-of-health with automated reporting
- One touch reporting: create standardized reports according to commonly used standards like EN 50160, IEEE 519, GOST 33073 or export data in PQDIF or NeQual compatible format for use with third party software
- Advanced analysis: choose any available logged parameter to create a highly customized view of logged measurements for advanced correlation of data
Fluke 4920613 Specifications
Voltage Range | 100 V to 500 V using safety plug input when powering from the measurement circuit |
Power Consumption | Maximum 50 VA (Max. 15 VA When Powered Using MA-C8 Adapter) |
Efficiency |  ≥ 68.2 % (In Accordance with Energy Efficiency Regulations) |
Maximum No-Load Consumption | <0.3 W Only When Powered Using IEC 60320 Input |
Mains Power Frequency | 50/60 Hz ± 15 % |
Battery | Li-ion 3.7 V, 9.2 Wh, Customer-Replaceable |
On-Battery Run Time | Typically 4 Hours |
Charging Time | <6 Hours |
Resolution | 16-bit Synchronous Sampling |
Input Signal Frequency | 50/60 Hz |
Data Storage | Internal Flash Memory (Not User Replaceable) |
Memory Size | Typical 20 Logging Sessions of 4 Weeks with 1-Minute Intervals and 500 Events |
Number of Inputs | 4 (3 Phases Referenced to Neutral) |
Maximum Input Voltage | 1000 Vrms, CF 1.7 |
Input Impedance | 10 MΩ |
Bandwidth | 42.5 Hz to 3.5 kHz |
Scaling | 1 |
Measurement Category | 1000 V CAT III/600 V CAT IV |
Dimensions | 9.1″ x 7.1″ x 2.1″ |